top of page

The TOR-60 unit is designed to measure the dielectric strength of transformer oil and other dielectric fluids according to IEC 60156, ASTM D877, ASTM D1816.

It is a fully automatic device that allows testing according to the procedures defined in these standards, as well as according to the user procedures specified in the appropriate section of the setup menu.

 

Operating principle

The core of the unit is the high voltage transformer and electronic modules. The unit operates by gradually increasing the voltage on the secondary winding of the high voltage transformer from zero to the maximum voltage, or to the voltage at which an electric breakthrough occurs in the dielectric fluid in the measuring cell installed on the high voltage contacts of the transformer.

The voltage in the secondary winding of the transformer occurs due to gradual increase of voltage in the primary winding supplied with sinusoidal voltage from the control inverter, one of the electronic modules.

 

Voltage increase is managed by a microcontroller through the control inverter. The control inverter is commanded by the unit control module.

During operation, AC (50-60Hz) voltage is supplied from the secondary winding terminals through the cell electrodes into the dielectric fluid in the measuring cell. The breakthrough occurs between the electrodes in the space filled with the dielectric fluid.

GlobeCore TOR-60 60kV Oil Breakdown Voltage Tester 60kV Transformer Oil

$5,299.00Price
  • no Item Value
    1 Operating AC voltage (internal rechargable battery), V 85 – 264
    2 Power frequency, Hz 48 – 63
    3 Power requirement, VA 70 max
    3 Max voltage output, kV Sinusoidal, up to 60 kV
    4 Output voltage measurement accuracy ±1 %
    5 Voltage increase rate, kV/sec 0,5 to 10 *
    6 Resolution of output voltage indication, V 100
    7 High voltage timeout after breakthrough, μs

    10 max, 4 typical

    8 Measuring cell volume, cm3 (in3) 500 (30)
    9 Ambient temperature measurement range, °С (°F) -10 – 50 (14 – 212)
    10 Temperature measurement resolution, °С (°F) 1 (34)
    11 Inbuilt printer Yes
    12 Operating temperature , °С (°F) -10 – 50 (14 – 122)
    13 Storage temperature, °С (°F) From – 20 (– 4) to + 60 (140)
    14 Relative humidity, % Up to 90 without condensation
    15 Dimensions, mm (in) 510 (20) Х 300 (12) Х 334 (13)
    16 Weight, kg (lbs), max 30 (66)
bottom of page