The Flir CM85-2 is an industrial power clamp meter with advanced power analysis and variable frequency drive (VFD) filtering functions required by electrical troubleshooters for full-scale equipment. Accurately analyze voltage in complex machinery by including harmonics, inrush, current, and phase rotation testing with a wide AC/DC voltage range and base accuracy of ±1%. Stream live data in real time from the CM85-2 to your mobile device over Bluetooth®. Using the METERLiNK® app, you can compare log files, create alarm thresholds, visualize trends, and create reports to share with team members.
Work with premier power and troubleshooting functions with this 1000 A True RMS power clamp that features Bluetooth connectivity up to 32' (10 m) and delivers in demanding applications and any environment. In addition, this power clamp features dual LED work lights to access dimly lit areas for faster and safer inspections. This product includes a Traceable Calibration Certificate with full Data and Uncertainties.
FLIR CM85-2-NIST True RMS Power Clamp with Bluetooth connectivity, 1000 A
Ordering Information
This product is only available to customers in the USA.
Please allow 2 - 3 weeks for this product to arrive.
This item comes with a 1 year warranty.
Included Accessories
- True RMS Power Clamp
- Set of CAT IV-600V Test Leads
- 6 x LR03 Alkaline Batteries
- Quick Start Guide
Specifications
Measurement Ranges and Accuracy Voltage DC:
99.99 V, ±(0.7% + 2 digits)
999.9 V, ±(0.7% + 2 digits)
AC:
0.05 to 99.99 V, ±(1% + 5 digits)
999.9 V, 50 to 500 HzVDF ACV:
0.05 to 99.99 V, 50 to 60 Hz ±(1% + 5 digits)
999.9 V, 50 to 60 Hz ±(1% + 5 digits)
ACA:
0.1 to 99.99 A, 50 to 60 Hz ±(2% + 5 digits)
999.9 A, 50 to 60 Hz ±(2% + 5 digits)Current DC:
99.99 A, ±(2% + 0.5 A)
999.9 A, ±(2% + 5 digits)
AC: 0.10 to 99.99 A, 50 to 60 Hz ±(2% + 5 digits)
999.9 A, >60 to 400 Hz ±(2.5% + 5 digits)Peak Hold ACV:
140 V, ±(3% + 15 digits)
1400 V, ±(3% + 15 digits)
ACA:
140 A, ±(3.5% + 15 digits)
1400 A, ±(3.5% + 15 digits)Frequency 20 to 99.99 Hz, ±(0.5% + 3 digits)
20 to 999.9 Hz, ±(0.5% + 3 digits)
0.02 to 9.999 kHz, ±(0.5% + 3 digits)Total Harmonic Distortion ACA/ACV 99.9%, ±(3% + 10 digits) Harmonic Distortion H01–H12: 99.9%, ±(5% + 10 digits)
H13-H25A: 99.9%, ±(10% + 10 digits)Inrush Current ACA 99.99 A, ±(3% + 0.3 A)
999.9 A, ±(3% + 5 digits)Watts DC:
9.999 kW (10 V, 5 A minimum), ±(3% + 0.05 kW)
99.99 kW (10 V, 5 A minimum), ±(3% + 0.5 kW)
999.9 kW (10 V, 5 A minimum), ±(3% + 10 digits)
AC:
9.999 kW (10 V, 5 A minimum), ±(3% + 10 digits)
99.99 kW (10 V, 5 A minimum), ±(3% + 10 digits)
999.9 kW (10 V, 5 A minimum), ±(3% + 10 digits)Power Factor -1 to 0 to 1, ±3° ±1 digit Resistance 999.9 Ω, ±(1% + 5 digits)
9.999 kΩ, ±(1% + 3 digits)
99.99 kΩ, ±(1% + 3 digits)Continuity 999.9 Ω, ±(1% + 5 digits) Diode 0.4 to 0.8 V, ±0.1 V Capacitance 3.999 μF, ±(1.9% + 8 digits)
39.99 μF, ±(1.9% + 8 digits)
39.99 μF, ±(1.9% + 8 digits)
3.999 mF, ±(1.9% + 8 digits)Measuring Rate 3 times per second Meter Data Jaw Opening 1.77" (45 mm) Bluetooth Range 32' (10 m) Data Recording Available via METERLiNK app Drop Test 4' (1.2 m) Category Rating CAT IV-600 V, CAT III-1000 V General Specifications Operating Ambient Temperatures and Relative Humidity 32 to 50°F (0 to 10°C), non-condensing
50 to 86°F (10 to 30°C), ≤80% RH
86 to 104°F (30 to 40°C), ≤75% RH
104 to 122°F (40 to 50°C), ≤45% RHStorage Temperature and Relative Humidity 14 to 122°F (-10 to 50°C)
0 to 80% RH (batteries not fitted)Temperature Coefficient 0.2 x (specified accuracy)/°C, <18°C, >28°C Operating Altitude 6562' (2000 m) Shock Vibration Random vibration per MIL‐PRF‐28800f Class 2 (5 to 55 Hz, 3 g maximum) Pollution Degree 2 Power Requirements 6 x 1.5 V AAA alkaline batteries Battery Life 50 hours with alkaline batteries (backlight, worklight, and Bluetooth off) Auto Power Off Approximately 30 minutes Certifications UL, CE, FCC, IC, UKCA, CSAUS Complies with Safety Standards IEC 61010-1:2010, IEC 61010-2-032:2012, IEC 61010-2-033:2012 EMC FCC: 47 CFR part 15 subpart B
CE:
EN IEC 61326-1:2021
EN IEC 61326-2-2:2021
EN 301 489-1 V2.2.3 (2019-11)
EN 301 489-17 V3.2.4 (2020-09)
RF:
ETSI EN 300 328 V2.2.2
EN 62479:2010
EN 50663:2017Dimensions 10.87 x 3.98 x 1.97" (276 x 101 x 50 mm) Weight 1.43 lbs (0.65 kg), including batteries Features
- VFD mode for superior accuracy on VFD-controlled equipment
- Inrush mode to capture AC Current spikes during start-up
- Bluetooth connectivity up to 32' (10 m)
- VFD mode increases accuracy when working on VFD-controlled equipment and conduct multiple conductor measurements with true RMS AC current up to 1000 A
- Purpose built for inspections: Dual LED lights eliminate the need to carry additional tools, and an ergonomic industrial design offers ease of use and operation
- Inpect at a safe disctance: Stream live readings in real time from the meter to your mobile device over Bluetooth using the METERLiNK app from a distance up to 32' (10 m)