top of page

This item is an excellent condition used Raytech TR-MARK III 250V Transformer Turns Tester 3-Phase. Calibrated to NIST Traceable Standards on November 12, 2026 with measured data report. Includes 3-phase test leads (X and H), standard power cable, and NIST traceable calibration certificate. All pictures are of the actual unit and accessories.

 

This item comes with a 180 day warranty. All functions are guaranteed to work or money will be refunded.

 

For customers in the USA, all purchases arrive cleared. ALL brokerage or customs fees are prepaid by us.  Your item arrives FOB destination.

 

International Buyers – Please Note: Import duties, taxes, and charges are not included in the item price or shipping cost. These charges are the buyer's responsibility. Please check with your country's customs office to determine what these additional costs will be prior to bidding or buying. For more information of clarification, please ask.

 

Will ship worldwide. We make our best efforts to get you the best shipping prices. Contact us for other international rates and we will be pleased to give you a quote. We accept VISA / Mastercard. Paypal is also accepted. Sales to within Canada are subject to 5% GST.  Ontario sales subject to 13% HST.

Raytech TR-MARK III 250V Transformer Turns Tester 3-Phase TTR NIST Calibrated

US$11,540.00Price
Quantity
  • Specifications and Description

    The TR-MARK III 250V is a 3-phase power transformer test instrument specially designed for professional turns ratio measurement. The professional turns ratio measurement is not just a typical pass/fail test to check that the deviation error is less than the limit values! For precise diagnosing and preventive maintenance, high precise measurement is required. In addition to precision, the TR-MARK III 250V provides useful tools such as the plotting tool on the colour touch display for this aim.

    The TR-MARK III 250V can perform the full turns ratio measurement in the least possible time and in a fully automatic easiest way. For a three-phase two-winding power transformer, only one time hook up of the test clamps is required. 

    • Extended test voltage measurement range of up to 250V
    • Automatic measurements of voltage, turns ratio, current, and phase displacement
    • Easy one-time hook up to the transformer
    • Automatic test voltage range
    • Displays deviation from a nominal ratio
    • Tap changer interface with graphic results
    • Load on test object <0.05 VA
    • Measures power transformers PTs and CTs
    • Automatic vector group detection
    • Displays % error vs. name plate value
    • Enhanced heavy-duty protection circuitry
    • Emergency stop push button immediately turns off output
    • Internal printer
    • Data storage of over 10,000 measurements
    • Simple-to-operate color LCD touch screen with backlight
    • Two USB interfaces
    Range Accuracy at 100V or 40V Accuracy at 10V Resolution
    0.8 … 2,000 ±0.06% Rdg ±1 LSD ±0.15% Rdg ±1 LSD 5 Digits
    2,001 … 4,000 ±0.1% Rdg ±1 LSD ±0.3% Rdg ±1 LSD 5 Digits
    4,001 … 13,000 ±0.3% Rdg ±1 LSD not specified 5 Digits
    13,001 … 16,000 ±0.4% Rdg ±1 LSD   5 Digits
           
    Range Accuracy at 250V   Resolution
    0.8 … 5,000 ±0.06% Rdg ±1 LSD   5 Digits
    5,001 … 10,000 ±0.1% Rdg ±1 LSD   5 Digits
    10,001 … 32,500 ±0.3% Rdg ±1 LSD   5 Digits
    32,501 … 40,000 ±0.4% Rdg ±1 LSD   5 Digits
           
    Current Accuracy   Resolution
    0 … 1A ±0.001A   0.1mA
           
    Phase Angle Accuracy   Resolution
    ±90 Degree ±0.05 Degree   0.01 Degree
           
    Turns Ratio Range 0.8 to 40,000  