top of page

This item is an excellent condition used Phenix HC-1 Circuit Breaker Test Set / Portable High Current Test Set. Will be calibrated to NIST Traceable Standards upon purchase. Includes test leads shown in our pictures and a NIST traceable calibration certificate. All pictures are of the actual unit and accessories.

 

This item comes with a 180 day warranty. All functions are guaranteed to work or money will be refunded.

 

For customers in the USA, all purchases arrive cleared. ALL brokerage or customs fees are prepaid by us.  Your item arrives FOB destination.

 

International Buyers Please Note: Import duties, taxes, and charges are not included in the item price or shipping cost. These charges are the buyer's responsibility. Please check with your country's customs office to determine what these additional costs will be prior to bidding or buying. For more information of clarification, please ask.

 

Will ship worldwide. We make our best efforts to get you the best shipping prices. Contact us for other international rates and we will be pleased to give you a quote. We accept VISA / Mastercard. Paypal is also accepted. Sales to within Canada are subject to 5% GST.  Ontario sales subject to 13% HST.

Phenix HC-1 Circuit Breaker Test Set Portable High Current Test Set Calibrated

$6,740.00Price
Quantity
    • Built for field or shop use
    • Combines a variable high current output with appropriate controls and instrumentation
    • Ideal for testing thermal, magnetic and solid-state motor overload relays as well as molded-case circuit breakers and ground fault trip devices
    • Provides a short duration output of 1000 amps through a typical 150 ampere molded-case circuitbreaker when an instataneous trip element must be tested
    • Unique auto-sensing feature makes these testers easy to operate
    • Sensing leads, which operate on either normally-open or normally-closed devices, are connected to the test object
    • Output current level can be easily pre-set
    • When the output is initiated the pre-set output current locks on and the timer starts
    • When the test set senses a change in state of the test object (NO to NC or NC to NO), the current shuts off and the timer stops
    • Memory feature of the currentmeter holds the peak current value until reset by operator

    Phenix Technologies HC1 Specs:

    • Input: 120 or 220 VAC, 50 or 60 Hz (must be specified)
      • 120 V: 20 Amp-Delay
      • 220 V: 10 Amp-Delay
    • Output:
      • 0-120 V @ 5 A
      • 0-24 V @ 25 A
      • 0-6 V @ 120 A
      • 0-3 V @ 240 A
    • Overload: 1000 Amps
    • Duty Cycle:
      • Continuous @ 100 %
      • 5 min ON / 15 min OFF @ 200%
      • 1 min ON / 5 min OFF @ 300%
      • 30 sec ON / 5min OFF @ 400%
    • Instrumentation:
      • Currentmeter: 3 1/2 digit LCD
        • Ranges: 0-1.999/19.99/199.9/1999 A
        • Accuracy: ± 0.5%
      • Timer: 6 digit LCD, in cycles or seconds
        • Range: 0-999999 cycles or 0-9999.99 sec.
        • ± 0.1% of reading
    • Dimensions/Weight: 21” W x 17” D x 13” H, 70 lbs.