Stationary, modular, comprehensive
Stationary meter designed to measure and record power supply parameters for compliance with standards and applicable laws, and with the ability to verify preset terms of a power sale/purchase contract.
Made in class A. Designed to be mounted on a DIN rail (with the possibility of mounting on a wall in a cabinet). Modular design allows adding new modules to expand the capabilities of the meter. The instrument allows measurements in 50 Hz, 60 Hz and 400 Hz networks.
The PQM-750 can be configured in various ways. Each set of built-in internal modules is a separate sales index for the analyzer. Need help choosing a configuration? Contact our Customer Service.
Measured parameters
Built-in software (web interface – webserver) allows you to configure the device and view actual data. It allows measurement of the following parameters.
- Phase RMS voltage U for L1, L2, L3+N/PE
- Phase-to-phase RMS voltages U for L12, L23, L31
- RMS currents I of all phases + N + PE
- Crest factor CF of voltages and currents
- Network frequency f for L1
- Active power P for L1, L2, L3
- Active power P1 (separated 50 Hz) for L1, L2, L3
- Reactive power Q for L1, L2, L3
- Reactive power Q1 (separated 50 Hz) for L1, L2, L3
- Apparent power S for L1, L2, L3
- Apparent power S1 (separated 50 Hz) for L1, L2, L3
- Three-phase total power P3F, Q3F, S3F
- Three-phase total power P13F, Q13F, S13F
- cosφ for L1, L2, L3, cosφ3F
- Power factor PF for L1, L2, L3, PF3F
- tgφ for L1, L2, L3, tgφ3F
- Distortion power D for L1, L2, L3
- Three-phase total distortion power D3F
- Distortion power factor DPF for L1, L2, L3
- Shape of phase voltages and currents for events
- Phase diagrams for currents and voltages
- Active energy for L1, L2, L3 – taken EP+ or given EP-.
- Three-phase active energy – drawn EP3F+ or given EP3F-
- Inductive reactive energy for L1, L2, L3 for consumption – EQL+
- Capacitive reactive energy for L1, L2, L3 for consumption – EQC+
- Three-phase reactive energy for consumption – inductive EQL3F+ and capacitive EQC3F+
- Apparent energy for L1, L2, L3 – ES
- Three-phase apparent energy ES3F
- Harmonics hn to 256th in current and voltage
- Interharmonics up to 256th in current and voltage
- Angles between current and voltage harmonics
- Monitoring of 2…150 kHz bandwidth
- UDC phase voltage components
- Shares of harmonic currents and voltages in relation to RMS value (%) – hnR
- Shares of harmonic currents and voltages in relation to the fundamental harmonic h1 (%) – hnF
- THDR for voltages and currents calculated against RMS value (%)
- THDF for voltages and currents calculated relative to the fundamental harmonic (%)
- TIDR for voltages and currents calculated against RMS value (%)
- TIDF for voltages and currents calculated relative to the fundamental harmonic (%)
- Active and reactive harmonic powers
- K-factor for I1, I2, I3, IN
- Factor K (Europe)
- Symmetrical voltage components: zero U0, direct U1, inverse U2
- Voltage values (V, %) of harmonic components of the order compatible (1, 4, 7,…), opposite (2, 5, 8,…), zero (3, 6, 9,…)
- Symmetrical components of current: zero I0, direct I1, inverse I2
- Values of currents (A, %) of harmonic components of the order direct (1, 4, 7,…), inverse (2, 5, 8,…), zero (3, 6, 9,…)
- Short-term light flicker factor Pst
- Long-term light flicker factor Plt
- Voltage unbalance
- Current unbalance
- Transients U up to 6000 V
- Ripple control signals
- Temperatures: Tw (analyzer internals), Tz1…Tz4 (1-wire)
Standards
Made in class A of the IEC 61000-4-30 standard, the instrument is compliant:
- Product standards:
- IEC 62586-1 – Power quality measurement in power supply systems – Part 1: Power quality instruments (PQI)
- IEC 62586-2 – Power quality measurement in power supply systems – Part 2: Functional tests and uncertainty requirements
- Standards for measuring network parameters:
- IEC 61000-4-30 – Electromagnetic compatibility (EMC) – Testing and measurement techniques – Power quality measurement methods
- IEC 61000-4-7 – Electromagnetic compatibility (EMC) – Testing and Measurement Techniques – General Guide on Harmonics and Interharmonics Measurements and Instrumentation for Power Supply Systems and Equipment Connected thereto
- IEC 61000-4-15 – Electromagnetic compatibility (EMC) – Testing and Measurement Techniques – Flickermeter – Functional and Design Specifications
- EN 50160 – Voltage characteristics of electricity supplied by public electricity networks
- Safety standards:
- IEC 61010-1 – Safety requirements for electrical equipment for measurement control and laboratory use. Part 1: General requirements
- IEC 61010-2-030 – Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 2-030: Particular requirements for equipment having testing or measuring circuits
- Standards for electromagnetic compatibility:
- EN 55032 – Electromagnetic compatibility of multimedia equipment – Emission Requirements
- IEC 61000-6-5 – Electromagnetic compatibility (EMC) – Part 6-5: Generic standards – Immunity for equipment used in power station and substation environment
Sonel PQM-750 LTE PRO Power Quality Analyzer