Stationary meter designed to measure and record power supply parameters for compliance with standards and applicable laws, and with the ability to verify preset terms of a power sale/purchase contract.

Made in class A. Designed to be mounted on a DIN rail (with the possibility of mounting on a wall in a cabinet). Modular design allows adding new modules to expand the capabilities of the meter. The instrument allows measurements in 50 Hz, 60 Hz and 400 Hz networks.

The PQM-750 can be configured in various ways. Each set of built-in internal modules is a separate sales index for the analyzer. Need help choosing a configuration? Contact our Customer Service.

 

 

Measured parameters

Built-in software (web interface – webserver) allows you to configure the device and view actual data. It allows measurement of the following parameters.

  • Phase RMS voltage U for L1, L2, L3+N/PE
  • Phase-to-phase RMS voltages U for L12L23L31
  • RMS currents I of all phases + N + PE
  • Crest factor CF of voltages and currents
  • Network frequency f for L1
  • Active power P for L1, L2, L3
  • Active power P1 (separated 50 Hz) for L1, L2, L3
  • Reactive power Q for L1, L2, L3
  • Reactive power Q1 (separated 50 Hz) for L1, L2, L3
  • Apparent power S for L1, L2, L3
  • Apparent power S1 (separated 50 Hz) for L1, L2, L3
  • Three-phase total power P3FQ3FS3F
  • Three-phase total power P13FQ13FS13F
  • cosφ for L1, L2, L3, cosφ3F
  • Power factor PF for L1, L2, L3, PF3F
  • tgφ for L1, L2, L3, tgφ3F
  • Distortion power D for L1, L2, L3
  • Three-phase total distortion power D3F
  • Distortion power factor DPF for L1, L2, L3
  • Shape of phase voltages and currents for events
  • Phase diagrams for currents and voltages
  • Active energy for L1, L2, L3 – taken EP+ or given EP-.
  • Three-phase active energy – drawn EP3F+ or given EP3F-
  • Inductive reactive energy for L1, L2, L3 for consumption – EQL+
  • Capacitive reactive energy for L1, L2, L3 for consumption – EQC+
  • Three-phase reactive energy for consumption – inductive EQL3F+ and capacitive EQC3F+
  • Apparent energy for L1, L2, L3 – ES
  • Three-phase apparent energy ES3F
  • Harmonics hn to 256th in current and voltage
  • Interharmonics up to 256th in current and voltage
  • Angles between current and voltage harmonics
  • Monitoring of 2…150 kHz bandwidth
  • UDC phase voltage components
  • Shares of harmonic currents and voltages in relation to RMS value (%) – hnR
  • Shares of harmonic currents and voltages in relation to the fundamental harmonic h1 (%) – hnF
  • THDR for voltages and currents calculated against RMS value (%)
  • THDF for voltages and currents calculated relative to the fundamental harmonic (%)
  • TIDR for voltages and currents calculated against RMS value (%)
  • TIDF for voltages and currents calculated relative to the fundamental harmonic (%)
  • Active and reactive harmonic powers
  • K-factor for I1, I2, I3, IN
  • Factor K (Europe)
  • Symmetrical voltage components: zero U0, direct U1, inverse U2
  • Voltage values (V, %) of harmonic components of the order compatible (1, 4, 7,…), opposite (2, 5, 8,…), zero (3, 6, 9,…)
  • Symmetrical components of current: zero I0, direct I1, inverse I2
  • Values of currents (A, %) of harmonic components of the order direct (1, 4, 7,…), inverse (2, 5, 8,…), zero (3, 6, 9,…)
  • Short-term light flicker factor Pst
  • Long-term light flicker factor Plt
  • Voltage unbalance
  • Current unbalance
  • Transients U up to 6000 V
  • Ripple control signals
  • Temperatures: Tw (analyzer internals), Tz1…Tz4 (1-wire)

Standards

Made in class A of the IEC 61000-4-30 standard, the instrument is compliant:

  • Product standards:
    • IEC 62586-1 – Power quality measurement in power supply systems – Part 1: Power quality instruments (PQI)
    • IEC 62586-2 – Power quality measurement in power supply systems – Part 2: Functional tests and uncertainty requirements
  • Standards for measuring network parameters:
    • IEC 61000-4-30 – Electromagnetic compatibility (EMC) – Testing and measurement techniques – Power quality measurement methods
    • IEC 61000-4-7 – Electromagnetic compatibility (EMC) – Testing and Measurement Techniques – General Guide on Harmonics and Interharmonics Measurements and Instrumentation for Power Supply Systems and Equipment Connected thereto
    • IEC 61000-4-15 – Electromagnetic compatibility (EMC) – Testing and Measurement Techniques – Flickermeter – Functional and Design Specifications
    • EN 50160 – Voltage characteristics of electricity supplied by public electricity networks
  • Safety standards:
    • IEC 61010-1 – Safety requirements for electrical equipment for measurement control and laboratory use. Part 1: General requirements
    • IEC 61010-2-030 – Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 2-030: Particular requirements for equipment having testing or measuring circuits
  • Standards for electromagnetic compatibility:
    • EN 55032 – Electromagnetic compatibility of multimedia equipment – Emission Requirements
    • IEC 61000-6-5 – Electromagnetic compatibility (EMC) – Part 6-5: Generic standards – Immunity for equipment used in power station and substation environment

 

 