top of page

Multifunction instrument for electrical installation safety testing, power quality analysis and EVSE safety testing.

 

COMBI521 carries out tests on electric systems in compliance with IEC/EN 61557-1 and therefore measurements of continuity of the protection cable, insulation resistance (with calculation of PI and DAR), overall earth resistance, RCDs type B, A and AC tripping time and current, line / fault impedance with calculation of prospective short circuit / fault current, phase sequence and conformity. COMBI521 also allows measuring and saving environmental parameters (illuminance, temperature), leakage current and electric quantities such as voltage, current, power factor, power and harmonics on single-phase systems. In combination with EV-TEST100, COMBI521 performs verification and control of electric car charging stations (EVSE) in accordance with IEC / EN 61851-1 and IEC / EN60364-7-722 standards.


COMBI521 is provided with the innovative AUTO function: by selecting this function and only setting the value of RCD current, COMBI521 carries out tests of overall earth resistance, RCD tripping time and insulation resistance in a sequence. At the end of the test, the device shows all results with the indication of compliance or non-compliance with the standards with simple OK or NOT OK symbols.

 

The internal memory allows saving the measures and subsequently transfer them onto the PC through the optical/USB connection. Thanks to the brand new HTAnalysis App, free to download for iOS and Android systems, COMBI521 is capable of transferring measured and recorded data onto tablets and smartphones, thus giving the operator the possibility to customize and share through HtCloud the result of their tests.
 

  • All electrical safety measurements as required by the international safety standards

  • AUTOMATIC test (no-trip ground resistance, RCD tripping time, insulation resistance) in a sequence

  • Continuity of protective conductors with 200mA

  • Insulation resistance up to 1000V, with dielectric absorption ratio D.A.R. and polarization index P.I.

  • Polarity test

  • Type A, AC, B General and Selective RCD tripping time and current

  • Line/Fault impedance, Phase-Phase, Phase-Neutral, Phase-PE (also at high resolution with optional accessory IMP57)

  • Coordination of MCBs and fuses

  • Global earth resistance

  • Phase sequence and conformity measurement

  • Measurement of leakage current

  • Measurement of electrical parameters in single-phase installations (V, A, W, VAR, VA, PF)

  • Measurement of environmental parameters through external probes (HT52/05 and HT53/05)

  • Internal memory and PC connection

  • Wi-Fi connection to Android and iOS smartphones and tablets

 

HT Instruments COMBI521 Multifunction Installation, PQA, EVSE Tester

US$1,429.00Price
Quantity
  • Ordering Information

    Please allow 4-5 weeks for this product to arrive

    This product comes with a 1 year manufacturer warranty

     

  • Included Equipment

    Calibration Report
    404-IECN Probe
    CO33X Leads
    5004-IECN Clip
    UNIVERSALKITCOMBI Probes, Leads and Clips
    C2006 USB and Downloadable Software
    4004-IECB Blue Probe
    5001-N Black Lead
    5001-B Blue Leads
    5001-R Red Lead

    5004-V Green Leads
    404-IECV Green Probe
    5004-IECB Blue Clip
    5004-IECR Red Clip
    5004-IECV Green Clip
    BORSA75 Soft Carrying Case
    404-IECR Red Probe
    SP-5100 Straps

  • Specifications

    Sequence of tests for the verification of electric columns With EV-TEST100 adapter
    AUTO test (Non-trip ground resistance, RCD, Insulation) in sequence  
    Measurement of polarization index P.I.  
    Insulation with voltage 50, 100, 250, 500, 1000VDC  
    Measurement of dielectric absorption ratio D.A.R.  
    Continuity of protective circuit with 200mA  
    Tripping time and current of RCDs type A, AC Standard, Selective B type up to 300mA
    Tripping time and current of F-type RCDs  
    Non-trip earth resistance  
    Loop/Line impedance, Phase-Phase, Phase-Neutral, Phase-PE  
    Loop/Line impedance Phase-Phase, Phase-Neutral, Phase-PE with high resolution (0.1mΩ) With optional accessory IMP57
    Percentage voltage drop on the line  
    Contact voltage  
    Phase sequence  
    Leakage current with optional clamp meter  
    Measurement of Voltage, Current, Active, Reactive, Apparent Power  
    Measurement of Cosphi, Power Factor  
    Voltage and current harmonics up to the 49th with THD 25ª
    Measurement of environmental parameters (°C,°F, %RH, Lux)  
    Test with remote lead PR400
    Help on line on the display  
    Internal memory for measured data saving  
    Integrated WiFi connection and compatibility with HTANALYSIS App  
    Optical/USB serial port for PC connection  
    Mechanical protection  
    Power supply  
    Protection category CAT IV 300V
    Weight in grams (batteries included) 1200
    Size (LxWx H) (mm) 222x162x57

Related Products