The HYDROCAL 1003 is an online monitoring system permanently mounted on the transformer. It measures continuously Moisture in Oil (H2O) and the most important faults gases Hydrogen (H2) and Carbon Monoxide (CO).
Analysis of the gases dissolved in power transformer oil is recognized as the most useful tool for early detection and diagnosis of incipient faults in transformers. In addition, water contamination deteriorates the performance of the oil as high moisture content increases the risk of corrosion and overheating. This is in particular when the water content reaches the saturation point of the oil and free water is formed.
Besides regular gas chromatographic analysis and off-line moisture analysis of the isolation oil of power transformers online monitoring systems gain more and more importance worldwide. By online monitoring of the key fault gases Hydrogen (H2) and Carbon Monoxide (CO) and Moisture in Oil (H2O) an additional potential of cost reductions and safety improvements can be achieved.
MTE HYDROCAL 1003 Online Transformer Monitoring System Gas in Oil Moisture
Ordering Information
Please allow 4 - 5 weeks lead time for this new product to arrive.
This product comes with a 1 year warranty from the manufacturer.
Features
- Individual analysis of the dissolved gas contents for Hydrogen (H2) and Carbon Monoxide (CO)
- Analysis of moisture (H2O) dissolved in transformer oil (both, relative humidity [%] and absolute humidity [ppm])
- Easy to mount on a transformer valve (G 1½" DIN ISO 228-1 or 1½" NPT ANSI B 1.20.1)
- Installation on the operational transformer without any operational interruption
- Advanced software (on the unit and via PC)
- Maintenance free system
- Communication interfaces ETHERNET (Option) 10/100 Mbit/s (copper-wired / RJ45 or fiber-optical / SC duplex), RS 232 and RS 485 to support MODBUS®RTU/ASCII, DNP3 proprietary communication and IEC 61850 protocols
- Optional 2G/3G modem with external adhesive antenna
- Optional DNP3 serial modem for SCADA connection
- Optional IEC 61850 modem for SCADA connection
Transformer Monitoring Functions
- Voltages and Currents - (via voltage and current transformers / transducer)
- Temperature Monitoring - Bottom and top oil temperature, ambient temperature (via additional temperature sensors)
- Cooling Stage/Tap Changer Position - (e.g. via current transducer)
- Free configuration - Analog inputs can be free allocated to any additional sensor